A07456
EPOS: Setpoint velocity limited
Message class:
Application/technological function faulted (17)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The actual setpoint velocity is greater than the parameterized maximum velocity (p2571) and is therefore limited.
Remedy:
- check the entered setpoint velocity.
- reduce the velocity override (CI: p2646).
- increase the maximum velocity (p2571).
- check the signal source for the externally limited velocity (CI: p2594).
A07457
EPOS: Combination of input signals illegal
Message class:
Application/technological function faulted (17)
Reaction:
NONE
Acknowledge:
NONE
Cause:
An illegal combination of input signals that are simultaneously set was identified.
Alarm value (r2124, interpret decimal):
0: Jog 1 and jog 2 (p2589, p2590).
1: Jog 1 or jog 2 and direct setpoint input/MDI (p2589, p2590, p2647).
2: Jog 1 or jog 2 and start referencing (p2589, p2590, p2595).
3: Jog 1 or jog 2 and activate traversing task (p2589, p2590, p2631).
4: Direct setpoint input/MDI and starting referencing (p2647, p2595).
5: Direct setpoint input/MDI and activate traversing task (p2647, p2631).
6: Start referencing and activate traversing task (p2595, p2631).
Remedy:
Check the appropriate input signals and correct.
F07458
EPOS: Reference cam not found
Message class:
Application/technological function faulted (17)
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
After starting the search for reference, the axis moved through the maximum permissible distance to search for the
reference cam without actually finding the reference cam.
Remedy:
- check the "reference cam" binector input (BI: p2612).
- check the maximum permissible distance to the reference cam (p2606).
- if axis does not have any reference cam, then set p2607 to 0.
See also: p2606 (EPOS search for reference reference cam maximum distance), p2607 (EPOS search for reference
reference cam present), p2612 (EPOS search for reference reference cam)
F07459
EPOS: No zero mark
Message class:
Application/technological function faulted (17)
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
After leaving the reference cam, the axis has traversed the maximum permissible distance between the reference
cam and zero mark without finding the zero mark.
Remedy:
- check the encoder regarding the zero mark
- check the maximum permissible distance between the reference cam and zero mark (p2609).
- use an external encoder zero mark (equivalent zero mark) (p0494).
See also: p0494 (Equivalent zero mark input terminal), p2609 (EPOS search for reference max distance ref cam and
zero mark)
F07460
EPOS: End of reference cam not found
Message class:
Application/technological function faulted (17)
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
During the search for reference, when the axis reached the zero mark it also reached the end of the traversing range
without detecting an edge at the binector input "reference cam" (BI: p2612).
Maximum traversing range: -2147483648 [LU] ... -2147483647 [LU]
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
4 Faults and alarms
4.2 List of faults and alarms
1089