Download Print this page

Siemens SINAMICS G120 List Manual page 1014

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

4 Faults and alarms
4.2 List of faults and alarms
Remedy:
- carry out a POWER ON (power off/on) for the Control Unit.
- carry out a hardware reset (RESET button, p0972).
N01101 (A)
CU: memory card not available
Message class:
Hardware/software error (1)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory card is not available for the drive.
Remedy:
Insert a memory card.
If Starter is not active, interrupt the USB connection to the PC
F01105 (A)
CU: Insufficient memory
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF1
Acknowledge:
POWER ON
Cause:
Too many data sets are configured on this Control Unit.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- reduce the number of data sets.
F01107
Save to memory card unsuccessful
Message class:
Hardware/software error (1)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A data save to the memory card was not able to be successfully carried out.
- Memory card is defective.
- insufficient space on memory card.
Fault value (r0949, interpret decimal):
1: The file on the RAM was not able to be opened.
2: The file on the RAM was not able to be read.
3: A new directory could not be created on the memory card.
4: A new file could not be created on the memory card.
5: A new file could not be written on the memory card.
Remedy:
- try to save again.
- replace the memory card or Control Unit.
F01110
CU: More than one SINAMICS G on one Control Unit
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
More than one SINAMICS G type power unit is being operated from the Control Unit.
Fault value (r0949, interpret decimal):
Number of the second drive with a SINAMICS G type power unit.
Remedy:
Only one SINAMICS G drive type is permitted.
F01111
CU: Mixed operation of drive units illegal
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Illegal operation of various drive units on one Control Unit:
- SINAMICS S together with SINAMICS G
- SINAMICS S together with SINAMICS S Value or Combi
Fault value (r0949, interpret decimal):
Number of the first drive object with a different power unit type.
Remedy:
Only power units of one particular drive type may be operated with one Control Unit.
1014
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890

Hide quick links:

Advertisement

loading