4 Faults and alarms
4.2 List of faults and alarms
Bit 18 = 1: PDS2 contactor is closed.
Bit 19 = 1: PDS3 contactor is closed.
Bit 20 = 1: PDS4 contactor is closed.
Bit 21 = 1: PDS5 contactor is closed.
Bit 22 = 1: PDS6 contactor is closed.
Bit 23 = 1: PDS7 contactor is closed.
Note:
PDS: Power unit Data Set
Remedy:
- check the monitoring time setting (p0255[5, 7]).
- check the wiring and control of the contactor.
- if required, replace the contactor.
F06310 (A)
Supply voltage (p0210) incorrectly parameterized
Message class:
Network fault (2)
Reaction:
NONE (OFF1, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The measured DC voltage lies outside the tolerance range after precharging has been completed.
Permissible range:
1.16 * p0210 < r0070 < 1.6 * p0210
Note:
The fault can only be acknowledged when the drive is switched off.
See also: p0210 (Drive unit line supply voltage)
Remedy:
- check the parameterized supply voltage and if required change (p0210).
- check the line supply voltage.
See also: p0210 (Drive unit line supply voltage)
A06921 (N)
Braking resistor phase asymmetry
Message class:
Braking Module faulted (14)
Reaction:
NONE
Acknowledge:
NONE
Cause:
- the three resistors of the braking chopper are not symmetrical.
- DC link voltage oscillations caused by fluctuating loads of the connected drives.
Remedy:
- check the feeder cables to the braking resistors.
- if required, increase the value for detecting asymmetry (p1364).
F06922
Braking resistor phase failure
Message class:
Braking Module faulted (14)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A phase failure for the brake resistor was detected.
Fault value (r0949, interpret decimal):
11: Phase U
12: Phase V
13: Phase W
See also: p3235 (Phase failure signal motor monitoring time)
Remedy:
Check the feeder cables to the braking resistors.
F07011
Drive: Motor overtemperature
Message class:
Motor overload (8)
Reaction:
OFF2 (NONE, OFF1, OFF3, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
KTY84/PT1000:
The motor temperature has exceeded the fault threshold (p0605) or the timer (p0606) after the alarm threshold was
exceeded (p0604) has expired. The response parameterized in p0610 becomes active. The alarm is withdrawn if the
response threshold for wire breakage or sensor not connected is exceeded (R > 2120 Ohm).
1076
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890