The nominal signal level of the encoder must lie in the range 375 mV to 600 mV (500 mV -25/+20 %).
The response thresholds are < 230 mV (observe the frequency response of the encoder) and > 750 mV.
A signal level of 500 mV peak value corresponds to the numerical value 5333 hex = 21299 dec.
Note:
If the amplitude is not within the tolerance bandwidth, then it cannot be used to initialize the start position.
Remedy:
- check that the encoder cables are routed in compliance with EMC.
- check the plug connections.
- replace the encoder or encoder cable.
- check the Sensor Module (e.g. contacts).
- check the Hall sensor box.
N32415 (F, A)
Encoder 2: Amplitude alarm track A or B (A^2 + B^2)
Message class:
Actual position/speed value incorrect or not available (11)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The amplitude (root of A^2 + B^2) for encoder 2 exceeds the permissible tolerance.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex:
yyyy = Angle
xxxx = amplitude, i.e. root of A^2 + B^2 (16 bits without sign)
The nominal signal level of the encoder must lie in the range 375 mV to 600 mV (500 mV -25/+20 %).
The response threshold is < 230 mV (observe the frequency response of the encoder).
A signal level of 500 mV peak value corresponds to the numerical value 299A hex = 10650 dec.
The angle 0 ... FFFF hex corresponds to 0 ... 360 degrees of the fine position. Zero degrees is present at the
negative zero crossover of track B.
Note for Sensor Modules for resolvers (e.g. SMC10):
The nominal signal level is at 2900 mV (2.0 Vrms). The response threshold is < 1414 mV (1.0 Vrms).
A signal level of 2900 mV peak value corresponds to the numerical value 3333 hex = 13107 dec.
Note when using the internal resolver evaluation (CU250S):
The nominal signal level is at 1300 mV. The response threshold is < 650 mV.
A signal level of 1300 mV peak value corresponds to the numerical value 16F3 hex = 5875 dec.
Note:
The analog values of the amplitude error are not measured at the same time with the hardware fault output by the
Sensor Module.
Remedy:
- check the speed range, frequency characteristic (amplitude characteristic) of the measuring equipment is not
sufficient for the speed range.
- check that the encoder cables and shielding are routed in compliance with EMC.
- check the plug connections.
- replace the encoder or encoder cable.
- check the Sensor Module (e.g. contacts).
- if the coding disk is soiled or the lighting aged, replace the encoder.
A32418 (F, N)
Encoder 2: Speed difference per sampling rate exceeded
Message class:
Actual position/speed value incorrect or not available (11)
Reaction:
NONE
Acknowledge:
NONE
Cause:
For an HTL/TTL encoder, the speed difference between two sampling cycles has exceeded the value in p0492.
The change to the averaged speed actual value - if applicable - is monitored in the current controller sampling time.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
See also: p0492 (Maximum speed difference per sampling cycle)
Remedy:
- check the tachometer feeder cable for interruptions.
- check the grounding of the tachometer shielding.
- if required, increase the setting of p0492.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
4 Faults and alarms
4.2 List of faults and alarms
1203