Download Print this page

Siemens SINAMICS G120 List Manual page 1133

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

A13001
Error in license checksum
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
When checking the checksum of the license key, an error was detected.
Remedy:
Compare the license key (p9920) entered with the license key on the certificate of license.
Re-enter the license key and activate (p9920, p9921).
F13009
Licensing OA application not licensed
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Cause:
At least one OA application which is under license does not have a license.
Note:
Refer to r4955 and p4955 for information about the installed OA applications.
Remedy:
- enter and activate the license key for OA applications under license (p9920, p9921).
- if necessary, de-activate unlicensed OA applications (p4956).
See also: p9920 (Licensing enter license key), p9921 (Licensing activate license key)
F13010
Licensing function module not licensed
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Cause:
At least one function module which is under license does not have a license.
Fault value (r0949, interpret hexadecimal):
Bit x = 1: The corresponding function module does not have a license.
Note:
Refer to p0108 or r0108 for the assignment between the bit number and function module.
Remedy:
- enter and activate the license key for function modules under license (p9920, p9921).
- if necessary, deactivate unlicensed function modules (p0108, r0108).
See also: p9920 (Licensing enter license key), p9921 (Licensing activate license key)
F13100
Know-how protection: Copy protection error
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Cause:
The know-how protection with copy protection for the memory card is active.
An error has occurred when checking the memory card.
Fault value (r0949, interpret decimal):
0: A memory card is not inserted.
1: An invalid memory card is inserted (not SIEMENS).
2: An invalid memory card is inserted.
3: The memory card is being used in another Control Unit.
12: An invalid memory card is inserted (OEM input incorrect, p7769).
13: The memory card is being used in another Control Unit (OEM input incorrect, p7759).
See also: p7765 (KHP configuration)
Remedy:
For fault value = 0, 1:
- insert the correct memory card and carry out POWER ON.
For fault value = 2, 3, 12, 13:
- contact the responsible OEM.
- Deactivate copy protection (p7765) and acknowledge the fault (p3981).
- Deactivate know-how protection (p7766 ... p7768) and acknowledge the fault (p3981).
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
4 Faults and alarms
4.2 List of faults and alarms
1133

Hide quick links:

Advertisement

loading