A30693 (F)
SI P2: Safety parameter settings changed, POWER ON required
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
Safety parameters have been changed; these will only take effect following a POWER ON.
Notice:
All changed parameters of the safety motion monitoring functions will only take effect following a POWER ON.
Alarm value (r2124, interpret decimal):
Parameter number of the safety parameter which has changed, necessitating a POWER ON.
Remedy:
- execute the function "Copy RAM to ROM".
- carry out a POWER ON (switch-off/switch-on).
C30700
SI Motion P2: STOP A initiated
Message class:
Safety monitoring channel has identified an error (10)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive is stopped via a STOP A (pulses are suppressed via the safety switch-off signal path of processor 1).
Possible causes:
- stop request from processor 1.
- pulses not suppressed after test stop selection.
- subsequent response to the message C30706 "SI Motion P2: SAM/SBR limit exceeded".
- subsequent response to the message C30714 "SI Motion P2: Safely Limited Speed exceeded".
- subsequent response to the message C30701 "SI Motion P2: STOP B initiated".
Remedy:
- remove the cause of the fault on the monitoring channel of processor 1.
- check the switch-off signal path of processor 2.
- carry out a diagnostics routine for message C30706.
- carry out a diagnostics routine for message C30714.
- carry out a diagnostics routine for message C30701.
- replace Power Module.
- replace Control Unit.
This message can be acknowledged using "Acknowledge internal event".
SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SBR: Safe Brake Ramp (safe brake ramp monitoring)
C30701
SI Motion P2: STOP B initiated
Message class:
Safety monitoring channel has identified an error (10)
Reaction:
NONE (OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive is stopped via a STOP B (braking along the OFF3 deceleration ramp).
As a result of this fault, after the speed threshold parameterized in p9360 is fallen below, message C30700 "STOP A
initiated" is output.
Possible causes:
- stop request from processor 1.
- subsequent response to the message C30714 "SI Motion P2: Safely Limited Speed exceeded".
- subsequent response to the message C30711 "SI Motion P2: Defect in a monitoring channel".
- subsequent response to the message C30707 "SI Motion P2: tolerance for safe operating stop exceeded".
Remedy:
- remove the cause of the fault on the monitoring channel of processor 1.
- carry out a diagnostics routine for message C30714.
- carry out a diagnostics routine for message C30711.
- carry out a diagnostics routine for message C30707.
Note:
This message can be acknowledged using "Acknowledge internal event".
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
4 Faults and alarms
4.2 List of faults and alarms
1155