4 Faults and alarms
4.2 List of faults and alarms
A32442 (F, N)
Encoder 2: Battery voltage pre-alarm
Message class:
Actual position/speed value incorrect or not available (11)
Reaction:
NONE
Acknowledge:
NONE
Cause:
When switched-off, the encoder uses a battery to back up the multiturn information. The multiturn information can no
longer be buffered if the battery voltage drops even further.
Remedy:
Replace battery.
A32443 (F, N)
Encoder 2: Unipolar CD signal level outside specification
Message class:
Actual position/speed value incorrect or not available (11)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The unipolar level (CP/CN or DP/DN) for encoder 2 is outside the permissible tolerance.
Alarm value (r2124, interpret binary):
Bit 0 = 1: Either CP or CN outside the tolerance.
Bit 16 = 1: Either DP or DN outside the tolerance.
The unipolar nominal signal level of the encoder must lie in the range 2500 mV +/- 500 mV.
The response thresholds are < 1700 mV and > 3300 mV.
Note:
The signal level is not evaluated unless the following conditions are satisfied:
- Sensor Module properties available (r0459.31 = 1).
- monitoring active (p0437.31 = 1).
Remedy:
- check that the encoder cables and shielding are routed in compliance with EMC.
- check the plug connections and contacts of the encoder cable.
- are the C/D tracks connected correctly (have the signal lines CP and CN or DP and DN been interchanged)?
- replace the encoder cable.
A32460 (N)
Encoder 2: Analog sensor channel A failed
Message class:
Actual position/speed value incorrect or not available (11)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The input voltage of the analog sensor is outside the permissible limits.
Alarm value (r2124, interpret decimal):
1: Input voltage outside detectable measuring range.
2: Input voltage outside measuring range set in p4673.
3: The absolute value of the input voltage has exceeded the range limit (p4676).
Remedy:
For alarm value = 1:
- check the output voltage of the analog sensor.
For alarm value = 2:
- check the voltage setting for each encoder period (p4673).
For alarm value = 3:
- check the range limit setting and increase it if necessary (p4676).
A32461 (N)
Encoder 2: Analog sensor channel B failed
Message class:
Actual position/speed value incorrect or not available (11)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The input voltage of the analog sensor is outside the permissible limits.
Alarm value (r2124, interpret decimal):
1: Input voltage outside detectable measuring range.
2: Input voltage outside the selected measuring range (p4675).
3: The absolute value of the input voltage has exceeded the range limit (p4676).
1206