A01319
Inserted component not initialized
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
Initialization is required for at least one inserted component.
This is only possible if the pulses are inhibited for all the drive objects.
Remedy:
Activate pulse inhibit for all drive objects.
A01321
Topology: Drive object number does not exist in configuration
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
p0978 contains a drive object number that does not exist.
Alarm value (r2124, interpret decimal):
Index of p0978 under which the drive object number can be determined.
Remedy:
Set p0009 to 1 and change p0978:
Rules:
- p0978 must include all of the drive object numbers (p0101).
- it is not permissible for a drive object number to be repeated.
- by entering a 0, the drive objects with PZD are separated from those without PZD.
- only 2 partial lists are permitted. After the second 0, all values must be 0.
- dummy drive object numbers (255) are only permitted in the first partial list.
A01322
Topology: Drive object number present twice in configuration
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
A drive object number is present more than once in p0978.
Alarm value (r2124, interpret decimal):
Index of p0978 under which the involved drive object number is located.
Remedy:
Set parameter p0009 = 1 and change p0978:
Rules:
- p0978 must include all of the drive object numbers (p0101).
- it is not permissible for a drive object number to be repeated.
- by entering a 0, the drive objects with PZD are separated from those without PZD.
- only 2 partial lists are permitted. After the second 0, all values must be 0.
- dummy drive object numbers (255) are only permitted in the first partial list.
A01323
Topology: More than two partial lists created
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
Partial lists are available more than twice in p0978. After the second 0, all must be 0.
Alarm value (r2124, interpret decimal):
Index of p0978 under which the illegal value is located.
Remedy:
Set p0009 to 1 and change p0978:
Rules:
- p0978 must include all of the drive object numbers (p0101).
- it is not permissible for a drive object number to be repeated.
- by entering a 0, the drive objects with PZD are separated from those without PZD.
- only 2 partial lists are permitted. After the second 0, all values must be 0.
- dummy drive object numbers (255) are only permitted in the first partial list.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
4 Faults and alarms
4.2 List of faults and alarms
1019