4 Faults and alarms
4.2 List of faults and alarms
F01505 (A)
BICO: Interconnection cannot be established
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A PROFIdrive telegram has been set (p0922).
An interconnection contained in the telegram was not able to be established.
Fault value (r0949, interpret decimal):
Parameter receiver that should be changed.
Remedy:
Establish another interconnection.
A01507 (F, N)
BICO: Interconnections to inactive objects present
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
There are BICO interconnections to an inactive/inoperable drive object.
The BI/CI parameters involved are listed in r9498.
The associated BO/CO parameters are listed in r9499.
The list of the BICO interconnections to other drive objects is displayed in r9491 and r9492 of the deactivated drive
object.
Note:
r9498 and r9499 are only written to, if p9495 is not set to 0.
Alarm value (r2124, interpret decimal):
Number of BICO interconnections found to inactive drive objects.
Remedy:
- set all open BICO interconnections centrally to the factory setting with p9495 = 2.
- make the non-operational drive object active/operational again (re-insert or activate components).
A01508
BICO: Interconnections to inactive objects exceeded
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum number of BICO interconnections (signal sinks) when deactivating a drive object was exceeded.
When deactivating a drive object, all BICO interconnections (signal sinks) are listed in the following parameters:
- r9498[0...29]: List of the BI/CI parameters involved.
- r9499[0...29]: List of the associated BO/CO parameters.
Remedy:
The alarm automatically disappears as soon as no BICO interconnection (value = 0) is entered in r9498[29] and
r9499[29].
Notice:
When re-activating the drive object, all BICO interconnections should be checked and if required, re-established.
F01510
BICO: Signal source is not float type
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested connector output does not have the correct data type. This interconnection is not established.
Fault value (r0949, interpret decimal):
Parameter number to which an interconnection should be made (connector output).
Remedy:
Interconnect this connector input with a connector output having a float data type.
F01511 (A)
BICO: Interconnection with different scalings
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested BICO interconnection was established. However, a conversion is made between the BICO output and
BICO input using the reference values.
- the BICO output has different normalized units than the BICO input.
- message only for interconnections within a drive object.
1036
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890