A07582 (F)
Encoder 2: Position actual value preprocessing error
Message class:
Actual position/speed value incorrect or not available (11)
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error has occurred during the position actual value preprocessing.
Remedy:
Check the encoder for the position actual value preprocessing.
See also: p2502 (LR encoder assignment)
A07584
Encoder 1: Position setting value activated
Message class:
Application/technological function faulted (17)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The position actual value is set to the value received via CI: p2515 while BI: p2514 = 1 signal. A possible system
deviation cannot be corrected.
Remedy:
Not necessary.
The alarm automatically disappears with BI: p2514 = 0 signal.
A07585
Encoder 2: Position setting value activated
Message class:
Application/technological function faulted (17)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The position actual value is set to the value received via CI: p2515 while BI: p2514 = 1 signal. A possible system
deviation cannot be corrected.
Remedy:
Not necessary.
The alarm automatically disappears with BI: p2514 = 0 signal.
A07587
Encoder 1: Position actual value preprocessing does not have a valid encoder
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The following problem has occurred during the position actual value preprocessing.
- an encoder data set has been assigned, however, the encoder data set does not contain any encoder data (p0400
= 0) or invalid data (e.g. p0408 = 0).
Remedy:
Check the drive data sets, encoder data sets.
See also: p0187 (Encoder 1 encoder data set number), p0188 (Encoder 2 encoder data set number), p0400
(Encoder type selection), p2502 (LR encoder assignment)
A07588
Encoder 2: Position actual value preprocessing does not have a valid encoder
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The following problem has occurred during the position actual value preprocessing.
- an encoder data set has been assigned, however, the encoder data set does not contain any encoder data (p0400
= 0) or invalid data (e.g. p0408 = 0).
Remedy:
Check the drive data sets, encoder data sets.
See also: p0187 (Encoder 1 encoder data set number), p0188 (Encoder 2 encoder data set number), p0400
(Encoder type selection), p2502 (LR encoder assignment)
A07590 (F)
Encoder 1: Drive Data Set changeover in operation
Message class:
Application/technological function faulted (17)
Reaction:
NONE
Acknowledge:
NONE
Cause:
A Drive Data Set changeover (DDS) with a change of the mechanical relationships and the encoder assignment
(p2502) was requested in operation.
Remedy:
To changeover the drive data set, initially, exit the "operation" mode.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
4 Faults and alarms
4.2 List of faults and alarms
1105