General information
2.5 Accessories
SINAMICS V90
Power
Frame
Rated
supply
size
power
(kW)
240 VAC
FSB
0.4
FSC
0.75
FSD
1.0
1.5
2.0
The above types for Type-E combination motor controllers are listed in compliance with both CE and UL/cUL standards.
1)
SINAMICS V90 400 V variant
SINAMICS V90
Power
Frame
Rated
supply
size
power
(kW)
3-phase,
FSAA
0.4
380 VAC to
FSA
0.75
480 VAC
1.0
FSB
1.5
2.0
FSC
3.5
5.0
7.0
The above types for Type-E combination motor controllers are listed in compliance with both CE and UL/cUL standards.
1)
Requirements for United States/Canadian installations (UL/cUL)
Suitable for use on a circuit capable of delivering not more than 65000 rms Symmetrical
Amperes, 480 VAC maximum for 400 V variants of drives or 240 VAC maximum for 200 V
variant drives, when protected by UL/cUL listed (JDDZ) fuse or type E combination motor
controller. For each frame size AA, A, B, C and D, use 75 °C copper wire only.
This equipment is capable of providing internal motor overload protection according to
UL508C.
For Canadian (cUL) installations the drive mains supply must be fitted with any external
recommended suppressor with the following features:
• Surge-protective devices; device shall be a Listed Surge-protective device (Category
• Rated nominal voltage 480/277 VAC, 50/60 Hz, 3-phase
• Clamping voltage VPR = 2000 V, IN = 3kA min, MCOV = 508 VAC, SCCR = 65 kA
• Suitable for Type 2 SPD application
• Clamping shall be provided between phases and also between phase and ground.
38
Recommended fuse
CE-compliant
3NA3 803 (10 A)
3NA3 805 (16 A)
3NA3 805 (16 A)
3NA3 810 (25 A)
3NA3 810 (25 A)
Recommended fuse type
CE-compliant
3NA3 801-6 (6 A)
3NA3 801-6 (6 A)
3NA3 803-6 (10 A)
3NA3 803-6 (10 A)
3NA3 805-6 (16 A)
3NA3 807-6 (20 A)
3NA3 807-6 (20 A)
3NA3 810-6 (25 A)
WARNING
code VZCA and VZCA7)
Type-E combination motor controller
UL/cUL-
Rated
compliant
current
listed (JDDZ)
(A)
fuse
10 A
2.8 to 4
20 A
5.5 to 8
20 A
7 to 10
25 A
10 to 16
25 A
10 to 16
Type-E combination motor controller
UL/cUL-
Rated
compliant
current
listed (JDDZ)
(A)
fuse
10 A
2.2 to 3.2
10 A
2.8 to 4
10 A
3.5 to 5
15 A
5.5 to 8
15 A
11 to 16
25 A
14 to 20
25 A
14 to 20
25 A
20 to 25
Rated
Rated
voltage
power
(VAC)
(hp)
230/240
3/4
230/240
2
230/240
3
230/240
5
230/240
5
Rated
Rated
voltage
power
(VAC)
(hp)
380/480
0.5
380/480
1
380/480
1.34
380/480
2
380/480
2.68
380/480
4.7
380/480
6.7
380/480
9.4
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E36037884-002
1)
Order number
3RV 2011-1EA10
3RV 2011-1HA10
3RV 2011-1JA10
3RV 2011-4AA10
3RV 2011-4AA10
1)
Order number
3RV 2021-1DA10
3RV 2021-1EA10
3RV 2021-1FA10
3RV 2021-1HA10
3RV 2021-4AA10
3RV 2021-4BA10
3RV 2021-4BA10
3RV 2021-4DA10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotics s-1fl6

Table of Contents