Siemens SINAMICS V90 Operating Instructions Manual page 302

Hide thumbs Also See for SINAMICS V90:
Table of Contents

Advertisement

Parameters
10.2 Parameter list
Par. No.
Name
p29006
Line supply voltage
Description: Nominal Line supply voltage, effective value of line to line voltage. Drive can operate within -15%
to +10% error.
For V90 400 V variant, the value range is 380 V to 480 V, default value is 400 V.
For V90 200 V variant, the value range is 200 V to 240 V, default value is 230 V.
p29007
RS485 protocol
Description: Set the communication protocol for the field bus interface:
0: No protocol
1: USS
2: Modbus
Note: Changes only become effective after power on. The parameter isn't influenced by default function.
p29008
Modbus control source
Description: Select the Modbus control source:
1: Setpoint and control word from Modbus PZD
2: No control word
No setpoint and control word from Modbus PZD
Note: Changes only become effective after power on.
p29009
RS485 baud rate
Description: Set the baud rate for the RS485 interface:
5: 4800 baud
6: 9600 baud
7: 19200 baud
8: 38400 baud
9: 57600 baud
10: 76800 baud
11: 93750 baud
12: 115200 baud
13: 187500 baud
Note: The change only becomes effective after power on. The parameter is not influenced by default function.
p29010
PTI: Selection of input
pulse form
Description: Selection of setpoint pulse train input form. After changing of p29010, reference point will lost,
A7461 will remind user to referencing again.
0: Pulse + direction, positive logic
1: AB phase, positive logic
2: Pulse + direction, negative logic
3: AB phase, negative logic
302
Min
Max
200
480
0
2
1
2
5
13
0
3
Factory
Unit
Data
Setting
type
400
V
U16
1
-
I16
2
-
I16
8
-
I16
0
-
U16
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E36037884-002
Effective
Can be
changed
IM
T
RE
T
RE
T
RE
T
IM
T