Fault
F7093: Drive: Test signal
error
Reaction: OFF3
Acknowledgement:
IMMEDIATELY
F7220: Drive: Master control
by PLC missing
Reaction: OFF1
Acknowledgement:
IMMEDIATELY
F7403: Lower DC link voltage
threshold reached
Reaction: OFF1
Acknowledgement:
IMMEDIATELY
F7404: Upper DC link voltage
threshold reached
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F7410: Current controller
output limited
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E36037884-002
Cause
The limit rotation of the motor (p29027) is
inappropriate.
The "master control by PLC" signal was
missing in operation.
Input for "master control by PLC" is
incorrect.
The higher-level control has withdrawn
the "master control by PLC" signal.
Data transfer via the fieldbus (mas-
ter/drive) was interrupted.
The DC link voltage monitoring is active
and the lower DC link voltage threshold
was reached in the "Operation" state.
The DC link voltage monitoring is active
and the upper DC link voltage threshold
was reached in the "Operation" state.
The condition "I_act = 0 and Uq_set_1
longer than 16 ms at its limit" is present
and can be caused by the following:
Motor not connected or motor contactor
open.
No DC link voltage present.
Motor Module defective.
11.2 List of faults and alarms
Remedy
Modify the value of parameter p29027.
Check the input for "master control by
PLC".
Check the "master control by PLC" signal
and, if required, switch in.
Check the data transfer via the fieldbus
(master/drive).
Check the line supply voltage.
Check the infeed.
Reduce the lower DC link threshold.
Switch out (disable) the DC link voltage
monitoring.
Check the line supply voltage.
Check the infeed module or the brake
module.
Increase the upper DC link voltage
threshold.
Switch out (disable) the DC link voltage
monitoring.
Connect the motor or check the motor
contactor.
Check the DC link voltage.
Check the Motor Module.
Diagnostics
331