Control functions
7.7 Communicating with the PLC
The table below formats a response for successful read operation.
Byte
Description
Header
01 h
0
Slave address
Number of following data bytes (20 h: 32 bytes ≙ 16 registers)
03 h
1
Function code (read)
20 h
2
User data
0002 h
3,4
40601: DS47 Control = 2 (request was executed)
2F0E h
5,6
40602: Function code 2F h (47), response lengths 14 bytes (0e h)
8001 h
7,8
40603: Request reference mirrored = 80 h,
response identifier = 1 (request parameter)
0202 h
9,10
40604: V90 = 2 h, number of parameters = 2
0301 h
11,12
40605: Format, number of elements of the first parameter
0001 h
13,14
40606: First parameter value = 1
0801 h
15,16
40607: Format, number of elements of the second parameter
4142 h
17,18
40608: Second paramter value = 12.15 (41426666 h)
6666 h
19,20
40609: Second paramter value
Write the PLC command from registers 40601 to 40609:
The table below formats a response for unsuccessful read operation (read request still not
completed).
Byte
Description
Header
01 h
0
Slave address
Number of following data bytes (20 h: 32 bytes ≙ 16 registers)
03 h
1
Function code (read)
20 h
2
User data
0001 h
3,4
40601: Check value 1 = request is processed
2F00 h
5,6
40602: Function 2F h(47), response length 0 (fault)
0004 h
7,8
40603: Error code:
issued)
230
0004 Response Not Ready (response has still not been
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E36037884-002