Control functions
7.7 Communicating with the PLC
The table below formats a response for successful write operation.
Byte
Description
Header
01 h
0
Slave address
Number of following data bytes (20 h: 32 bytes ≙ 16 registers)
03 h
1
Function code (read)
20 h
2
User data
0002 h
3,4
40601: DS47 Control = 2 (request was executed)
2F04 h
5,6
40602: Function code 2F h (47), response length 4 bytes
8002 h
7,8
40603: Request reference mirrored = 80 h,
response identifier = 2 (change parameter)
0202 h
9,10
40604: V90 = 2 h, number of parameters = 2
Write the PLC command from registers 40601 to 40604:
The table below formats a response for unsuccessful write operation (write request still not
completed).
Byte
Description
Header
01 h
0
Slave address
Number of following data bytes (20 h: 32 bytes ≙ 16 registers)
03 h
1
Function code (read)
20 h
2
User data
0001 h
3,4
40601: DS47 Control = 1 (request is processed)
2F00 h
5,6
40602: Function 2F h(47), response length 0 (fault)
0004 h
7,8
40603: Error code:
issued)
232
0004 Response Not Ready (response has still not been
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E36037884-002