Siemens SINAMICS V90 Operating Instructions Manual page 229

Hide thumbs Also See for SINAMICS V90:
Table of Contents

Advertisement

Example: p1215 and p1120 read acyclically
The table below formats a request to read the parameter values of p1215 and p1120 from
slave number 1.
Byte
Header
01 h
0
10 h
1
0258 h
2,3
000A h
4,5
14 h
6
User data
0001 h
7,8
2F10 h
9,10
8001 h
11,12
0202 h
13,14
1001 h
15,16
04BF h
17,18
0000 h
19,20
1001 h
21,22
0460 h
23,24
0000 h
25,26
Write the PLC command from registers 40601 to 40610:
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E36037884-002
Description
Slave address
Function code (write multiple)
Register start address
Number of registers to be read (40601 ... 40610)
Number of data bytes (10 registers, each 2 bytes = 20
bytes)
40601: DS47 Control = 1 (activate request)
40602: Function 2F h (47), request length 16 bytes (10 h)
40603: Request reference = 80 h, request identifier = 1 h
40604: V90 = 2 h, number of parameters = 2
40605: Attribute, number of elements of the first parame-
ter
40606: First parameter number = p1215
40607: First parameter subindex = 0
40608: Attribute, number of elements of the second parame-
ter
40609: Second paramter number = p1120
40610: Second parameter subindex = 0
Control functions
7.7 Communicating with the PLC
229