Diagnostics
11.2 List of faults and alarms
Fault
F7412: Commutation angle
incorrect (motor model)
Reaction: ENCODER
Acknowledgement:
IMMEDIATELY
F7420: Drive: Current set-
point filter natural frequency >
Shannon frequecy
F7430: Changeover to open-
loop torque controlled opera-
tion not possible
Reaction: OFF2
Acknowledgement: POWER
ON
F7431: Changeover to en-
coderless operation not pos-
sible
Reaction: OFF2
Acknowledgement: POWER
ON
332
Cause
An incorrect commutation angle was de-
tected that can result in a positive coupling
in the speed controller.
Possible causes:
The motor encoder is incorrectly ad-
justed with respect to the magnet posi-
tion.
The motor encoder is damaged.
Data to calculate the motor model has
been incorrectly set.
Pole position identification might have
calculated an incorrect value when ac-
tivated.
The motor encoder speed signal is
faulted.
The control loop is instable due to
incorrect parameterization.
One of the filter natural frequencies is
greater than the Shannon frequency.
For encoderless operation, the converter
cannot change over to closed-loop torque-
controlled operation.
For closed-loop torque control, the con-
verter cannot change over to encoderless
operation.
Remedy
If the encoder mounting was changed, re-
adjust the encoder.
Replace the defective motor encoder.
Correctly set the motor stator resistance,
cable resistance and motor-stator leakage
inductance.
Calculate the cable resistance from the
cross-section and length, check the in-
ductance and stator resistance using the
motor data sheet, measure the stator re-
sistance, e.g. using a multimeter - and if
required, again identify the values using
the stationary motor data identification.
With pole position identification activated,
check the procedure for pole position
identification and force a new pole posi-
tion identification procedure by means of
de-selection followed by selection.
Reduce the numerator or denominator
natural frequency of the current setpoint
filter involved.
Switch out the filter involved (p1656).
Do not attempt to change over to closed-
loop torque-controlled operation.
Check the encoder cable connection.
Do not attempt to change over to encoder-
less operation.
Check the encoder cable connection.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E36037884-002