Appendix A - User Interface Display

Setup #5 Screen

A
Overview
This screen controls settings for the pressure sensors.
These values are used for triggering errors.
#1 to #6 Buttons
Press to navigate to the Setup Screen with that number.
For example, press #3 to navigate to Setup Screen #3.
Inlet, Outlet Offset
The inlet, outlet offset values are used to tune the pres-
sure transducer. If the pressure transducers do not reg-
ister zero pressure when there is no material in the
system, enter a value to shift the pressure value to zero.
For example, if 15 psi is shown, enter -15 psi to shift the
value to 0.
92
Min/Max Inlet/Outlet Limits
These limit values are used to set the acceptable range
of values for dispensing. If values are outside of this
range during dispensing the machine will issue an
alarm. See Errors on page 31.
PSI, BAR
Set the unit of measure for pressure system-wide.