System Setup

Configure Delay Settings

Set on and off delays (in milliseconds) for the dispense
valve.
1. With the system in setup mode, press
igate to the Delay Settings screen.
F
. 13
IG
2. Press the On Delay field and enter a desired delay
value in milliseconds. Default is zero milliseconds.
3. Press the Off Delay field and enter e desired value
in milliseconds. Default is zero milliseconds.
20

Adjust Pressure Sensors

Set pressure offsets and pressure limits.
1. With the system in setup mode, press
to nav-
igate to the Pressure Sensor screen.
F
. 14
IG
2. Set the desired offset for the inlet and outlet pres-
sures. Remove all pressure on the sensors, and
then adjust the offset so the measured value
reads 0.
NOTE: Offsets are set at the factory.
3. Set the desired minimum and maximum pressure
limits for the inlet and outlet.
NOTE: These values may need changed after the
system has gone through the Startup procedure.
to nav-