11.5 Selection example of wires

The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
Table 11.1 shows examples for using the 600 V Grade heat-resistant polyvinyl chloride insulated wire (HIV
wire).
POINT
To comply with the IEC/EN/UL/CSA standard, use the wires shown in app. 2 for
wiring. To comply with other standards, use a wire that is complied with each
standard.
Selection conditions of wire size are as follows.
Construction condition: Single wire set in midair
Wiring length: 30 m or shorter
1) Power lead
Power supply
Regenerative option
3) Regenerative option lead
Table 11.1 Wire size selection example (HIV wire)
Servo amplifier
MR-JE-10A
MR-JE-20A
MR-JE-40A
MR-JE-70A
MR-JE-100A
MR-JE-200A
(3-phase power
supply input)
MR-JE-200A
(1-phase power
supply input)
MR-JE-300A
Note 1. The wire size shows applicable size of the servo amplifier connector. For wires
connecting to the servo motor, refer to "HG-KN/HG-SN Servo Motor Instruction
Manual".
2. Be sure to use the size of 2 mm
standard.
Servo amplifier
L1
U
L2
V
L3
W
C
P+
1) L1/L2/L3/
2 (AWG 14)
2 (AWG 14)
3.5 (AWG 12)
2 (AWG 14)
2
when corresponding to IEC/EN/UL/CSA
11 - 18
M
2) Servo motor power supply lead
Wire [mm
2
]
2) U
/
V
/
W
3) P+
C
/
(Note 1)
AWG 18 to 14
(Note 2)
AWG 16 to 10
/