3 SPECIFICATIONS
BFM number
Attribute
Application
Decimal
(Hexadecimal)
512 to 513
R/W
(200 to 201
)
H
Router relay
514 to 515
parameter
R/W
(202 to 203
)
H
setting area
516 to 1599
(204 to 63F
)
H
BFM number
Attribute
Application
Decimal
(Hexadecimal)
1600
Re-
R/W
(640
)
initialization
H
1601
COM.ERR.
R/W
(641
)
Off
H
3 - 18
(e)
Router relay parameter setting area (BFM #512 to 1599)
Sub-net mask
Default router IP address
System area
(f)
Open/close control (BFM #1600 to 1663)
• Write value
Re-initialization request
0001H : Re-initialization ([COM.ERR.] LED OFF)
0002H : Re-initialization after reading data in Flash ROM
([COM.ERR.] LED OFF)
0005H : Re-initialization ([COM.ERR.] LED retains status.)
0006H : Re-initialization after reading data in Flash ROM
([COM.ERR.] LED retains status.)
• Read value
0008H
: During re-initialization
8000H
: At re-initialization completion
C000H
: At re-initialization error
• In the re-initialization standby, the write value is read directly.
[COM.ERR.] Off request
• Write value
0001H: [COM.ERR.] LED Off request
(In standby until extinction)
• Read value
0002H: Stores at normal completion
0001H is read while ready until LED OFF operation starts
Name
Name
MELSEC-F
Initial value
Flash ROM
Reference
Decimal
save
(Hexadecimal)
0
Section 5.3
(0
)
H
Initial value
Flash ROM
Reference
Decimal
save
(Hexadecimal)
0
(0000
)
H
0
(0000
)
H