9 WHEN COMMUNICATING DATA USING THE MC PROTOCOL
(Data name)
External
*
device side
(Example)
03
FF
0A
H
H
(Data name)
PLC side
(Example)
9 - 31
NOTE
C200 to C255 (Current Values) Batch Write
Since C200 toC255 are 32 bit devices, the device points should be specified twice
as much as the points actually read.
Also, make sure that the device points are specified by even number.
If they are specified by odd number, the batch read cannot be performed. (Error
code 57
will be stored)
H
Example) When 32 points are written at one access from C220 to 251 in the PLC on
which the Ethernet module is mounted.
(1) When communicating in binary code
Head device
H
L
-
-
-
-
L
00
DC
00
00
00
4E
43
H
H
H
H
H
H
H
CN220
32 points x 2 = 64word
(2 bites x 2) x 32 = 128 bytes
Head data
Low
High
16bit
16bit
H
L - H
L - H
40
00
4E
61
BC
00
H
H
H
H
H
H
H
12345678=00BC614E
Last data
Low
High
16bit
16bit
L - H
L - H
40
01
B9
02
H
H
H
H
45678912=02B90140
H
H