8 COMMUNICATION USING MC PROTOCOL

8.1.3 Access Timing on the PLC Side

Read/write command
(command)
PLC
8 - 4
The following diagram illustrates the access timing on the PLC side when an external
device accesses the PLC via the Ethernet module.
1)
Ethernet module
2)
STEP 0
END
STEP 0
END processing
Processing of the command from the external device
1)
A command message is transmitted from the external device to the
PLC side.
2)
Upon receiving a command message from the external device, the
FX
3U
PLC according to the content of the command.
3)
The PLC reads/writes data according to the request from the external
device at the time of executing the sequence program's END
instruction, and passes the processing result to the Ethernet module.
4)
Upon receiving the processing result from the PLC, the Ethernet
module sends a response message including the processing result to
the external device that originated the request.
1 The ACK response shown in the diagram is sent/received between the
Ethernet module and the external device respectively when the access
via the Ethernet module is performed by TCP/IP communication.
It is different from the response to the processing requested by the
external device in the command message (the processing result).
When access via the Ethernet module is performed by UDP/IP, the
ACK response indicated by
NOTE
Regarding the scan time of the PLC
1)
While the PLC is performed by required command, access command to the
Ethernet module and the PLC is processed during every END processing.
(The scan time becomes longer according to the amount of time it takes to
process the command.)
2)
When multiple external devices issue access requests to a single station at the
same time, the processing requested from the external devices may have to
wait for multiple END processing executions depending on the timing of the
requests.
External device
Reply to the
(*1)
command (response)
ACK
(*1)
ACK
4)
3)
END
STEP 0
END
END processing
END processing
-ENET on the PLC side sends a data read/write request to the
STEP 0
END
1 is not sent.