Terminal strips behind the lower front door

All terminals with reference potential "GND" are connected with one another in the inverter.
Reference potentials for DI 1, DI 3 und DI 5, electrically isolated from "GND"
Reference potential for DI 0, DI 2, DI 4 and DI 6, electrically isolated from "GND"
Reference potential for DI 16 ... DI 19, electrically isolated from "GND"
Image 4-10
Interconnection example of the digital inputs with external 24 V power supplies
Interconnecting the reference potential of the digital inputs
Table 4- 9
Supply
You are using an external 24
V supply
You are using the internal 24
V supply at terminal 9
88
Supply options for the digital inputs
Reference potential interconnection
As shown above, connect the reference potential of the external 24-V
supply to the reference potential of the corresponding digital input.
Connect the appropriate reference potential of the digital input to
GND.