Siemens sinamics G120 Operating Instructions Manual page 62

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Installing
4.4 Installing Power Modules
Depth with Control Unit and Operator Panel
FSA ... FSC:
FSD ... FSF
Drilling dimensions and cooling air clearances
Table 4- 2
Frame size
FSA
FSB
FSC
FSD
FSE
FSF
62
• with Control Unit:
• With Control Unit and blanking cover / BOP-2:
• With Control Unit and IOP:
• with Control Unit:
• With Control Unit and blanking cover / BOP-2:
• With Control Unit and IOP:
Drilling dimensions, cooling clearances and fixing
Drilling dimensions (mm)
a
b
186
62.3
281
80
343
120
430
170
509
230
680
270
Cooling air clearances
(mm)
c
Top
Bottom
6
80
100
6
80
100
6
80
100
15
300
350
11
300
350
13
300
350
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
+ 62 mm
+ 73 mm
+ 84 mm
+ 18.5 mm
+ 29.5 mm
+ 40.5 mm
Fixing
Front
Torque [Nm]
100
3 x M4 / 2.5
100
4 x M4 / 2.5
100
4 x M5 / 3.0
100
4 x M6 / 6.0
100
4 x M6 / 10
100
4 x M8 / 25
Converter with CU250S-2 Control Unit