Technical Data; Technical Data, Cu250S-2 Control Unit - Siemens sinamics G120 Operating Instructions Manual

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Technical data

10.1

Technical data, CU250S-2 Control Unit

Feature
Fieldbus interfaces
Operating voltage
Current drain when supplied via 31
and 32
Power loss
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Data
CU250S-2
CU250S-2 DP
CU250S-2 PN
CU250S-2 CAN
You have two options for the Control Unit power supply:
Supply from the Power Module.
The sum of all of the currents of the following interfaces is limited to 0.8 A:
Encoder power supply
DRIVE-CLiQ
Power supply for the Operator Panel
Analog outputs
24 V output voltage (terminal 9)
24 V PROFIBUS teleservice
Resolver excitation
If a short-circuit occurs at the output terminals when the CU is fully loaded, then
the Power Module overcurrent protection acts, and the inverter is tripped with
overcurrent (Power Module and Control Unit).
External supply via terminals 31 and 32 with 20.4 ... 28.8 VDC.
Use a power supply with protective extra low voltage (PELV according to EN
61800-5-1), Class 2.
The 0 V of the power supply must be connected to the PE of the plant/system
through a low-ohmic connection.
The power supply is electrically isolated from the other terminal strip.
max. 2 A
12.0 W
With RS485 interface for the
following protocols:
USS
Modbus RTU
With PROFIBUS interface
With RJ45 connector for the
following fieldbuses:
PROFINET
EtherNet/IP
With CANopen interface
plus the power loss of all output voltages
10
Article numbers:
Overview of Control
Units (Page 29)
427