Load Monitoring - Siemens sinamics G120 Operating Instructions Manual

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Advanced commissioning
6.7 Application-specific functions
6.7.10.2

Load monitoring

The load monitoring comprises the following components:
● Load failure monitoring
● Monitoring for torque deviation
● Speed deviation monitoring
If the load monitoring detects a load failure, the inverter issues fault F07936. For a torque
and speed deviation, as response, you can either set an alarm or a fault. Details are
provided in the following descriptions.
Settings
Table 6- 45
Parameters
p2193
Load failure monitoring
Principle of operation
Using this function, the inverter monitors the speed or velocity of a machine component. The
inverter evaluates whether an encoder signal is present. If the encoder signal fails for a time
that can be adjusted, then the inverter signals a fault.
Examples of how the function can be used:
● Gearbox monitoring for traction drives and hoisting gear
● Drive belt monitoring for fans and conveyor belts
● Blocking protection for pumps and conveyor belts
Image 6-60
304
Setting options for load monitoring
Description
Load monitoring configuration (factory setting: 1)
0: Monitoring deactivated
1: Torque and load failure monitoring
2: Speed and load failure monitoring
3: Load failure monitoring
Function plan and time response of load-interruption monitoring
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Converter with CU250S-2 Control Unit