Siemens sinamics G120 Operating Instructions Manual page 460

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Technical data
10.2 Technical data, Power Modules
Table 10- 37 PM240 frame sizes GX, 3-phase 380 ... 480 VAC
Article no. - without filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to UL (SIEMENS)
Fuse according to UL (Class J)
Power loss,
Required cooling air flow
Weight
Applications with UL certification
Table 10- 38 Frame size A ... C
Class J fuses
Class K-1 or K-5 fuses
Semiconductor fuses R/C (JFHR2, E167357)
Table 10- 39 Frame size D ... GX
Only with Class J or R/C semiconductor fuses
(JFRH2)
460
6SL3224-...
...0XE41-3UA0
160 kW
297 A
302 A
132 kW
245 A
250 A
3NE1333-2
3.9 kW
360 l/s
176 kg
...0XE41-6UA0
200 kW
354 A
370 A
160 kW
297 A
302 A
3NE1333-2
---
---
4.4 kW
360 l/s
176 kg
Suitable for plants/systems with a max. current of 65
kA (symmetrical, rms value), max. 480 VAC
Suitable for plants/systems with a max. current of 10
kA (symmetrical, rms value), max. 480 VAC
Suitable for plants/systems with a max. current of 5
kA (symmetrical, rms value), max. 480 VAC
Suitable for plants/systems with a max. current of 65
kA (symmetrical, rms value), max. 480 VAC
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
...0XE42-0UA0
240 kW
442 A
477 A
200 kW
354 A
370 A
3NE1436-2
---
5.5 kW
360 l/s
176 kg
Converter with CU250S-2 Control Unit