Advertisement

6.2.2.4

Analog inputs

Overview
Connector inputs are marked with "CI" in the parameter list of the List Manual.
Defining the analog input type
The inverter offers a series of default settings, which you can select using parameter p0756:
AI 0
AI 1
In addition, you must set the switch belonging to the analog input. You can
find the switch on the Control Unit behind the lower front door.
• Voltage input: Switch position U (factory setting)
• Current input: Switch position I
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Interconnecting signals in the inverter (Page 494)
Unipolar voltage input
Unipolar voltage input monitored
Unipolar current input
Unipolar current input monitored
Bipolar voltage input
No sensor connected
Unipolar voltage input
Unipolar voltage input monitored
Unipolar current input
Unipolar current input monitored
Bipolar voltage input
No sensor connected
Advanced commissioning
Changing the function of an analog input:
1. Define the analog input type using
parameter p0756[x] and the switch on the
inverter.
2. You define the analog input function by
interconnecting parameter p0755[x] with
a connector input CI of your choice.
0 V ... +10 V
+2 V ... +10 V
0 mA ... +20 mA
+4 mA ... +20 mA
-10 V ... +10 V
0 V ... +10 V
+2 V ... +10 V
0 mA ... +20 mA
+4 mA ... +20 mA
-10 V ... +10 V
6.2 Inverter control
p0756[0] =
0
1
2
3
4
8
p0756[1] =
0
1
2
3
4
8
157