6. Optimize the controller by adapting the ratio of the moments of inertia of the load and
motor (p0342):
7. Switch off the motor.
8. Start a new calculation of the speed controller: p0340 = 4.
9. Switch on the motor.
10.Over the complete speed range check whether the speed control responds satisfactorily
with the optimized settings.
You have optimized the speed controller.
When necessary, set the ramp-up and ramp-down times of the ramp-function generator
(p1120 and p1121) back to the value before optimization.
Mastering critical applications
The drive control can become unstable for drives with a high load moment of inertia and
gearbox backlash or a coupling between the motor and load that can possibly oscillate. In
this case, we recommend the following settings:
● Increase the smoothing of speed actual value p1452.
● Increase the integral time: T
● If the closed-loop speed control no longer has an adequate dynamic performance after
these measures, then increase the P gain K
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Initially, the actual speed follows the setpoint speed; however, it
then overshoots the setpoint speed.
Increase p0342
Initially, the actual speed exceeds the setpoint speed; however,
it does not overshoot but instead approaches the setpoint speed
"from below".
Reduce p0342
≥ 4 × p1452.
I
step-by-step.
P
Advanced commissioning
6.5 Motor control
237