Siemens sinamics G120 Operating Instructions Manual page 229

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Characteristics after selecting the application class Standard Drive Control
Selecting application class Standard Drive Control reduces the number of characteristics and
the setting options:
● A linear and a parabolic characteristic are available.
● Selecting a technological application defines the characteristic.
● The following cannot be set - ECO mode, FCC, the programmable characteristic and a
specific voltage setpoint.
Image 6-37
Table 6- 35
Linear and parabolic characteristics
Requirement
Application examples
The required
Conveyor belts, roller
torque is inde-
conveyors, chain con-
pendent of the
veyors, eccentric worm
speed
pumps, compressors,
extruders, centrifuges,
agitators, mixers
The required
Centrifugal pumps,
torque increases
radial fans, axial fans
with the speed
Additional information on the characteristics can be found in the parameter list and in the
function diagrams 6851 ff of the List Manual.
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
The closed-loop starting current control optimizes the speed control at low speeds
The inverter compensates the voltage drop across the motor stator resistance
Characteristics after selecting Standard Drive Control
Remark
-
Lower losses in the motor and inverter
than for a linear characteristic.
Advanced commissioning
6.5 Motor control
Characteristic
Parameter
Linear
p0501 = 0
Parabolic
p0501 = 1
229