10.2.3.2
Power-dependent data, PM340
Air-cooled Power Modules
Table 10- 40 PM340, IP20, frame size A, 1 AC 200 V ... 240 V
Article No. - without filter
Article No. - with filter
Rated power
Rated input current
Rated output current
Base load current
Maximum current
Current for S6 duty
Fuse according to IEC
Fuse according to UL
Power loss
Required cooling air flow
Cross section of line and motor cables
Tightening torque for line and motor cables
Weight without filter
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
6SL3210...
...1SB11-0UA0
6SL3210...
...1SB11-0AA0
0.12 kW
2.2 A
0.9 A
0.8 A
2.0 A
1.4 A
6 A
6 A Class J
0.06 kW
5 l/s
1 ... 2.5 mm
18 ... 14 AWG
0.5 Nm / 4 lbf in
1.2 kg
10.2 Technical data, Power Modules
...1SB12-3UA0
...1SB12-3AA0
0.37 kW
6 A
2.3 A
2.0 A
4.6 A
3.3 A
10 A
10 A Class J
0.075 kW
5 l/s
1 ... 2.5 mm
2
2
18 ... 14 AWG
0.5 Nm / 4 lbf in
1.3 kg
Technical data
...1SB14-0UA0
...1SB14-0AA0
0.75 kW
10 A
3.9 A
3.4 A
7.8 A
5.5 A
15 A
15 A Class J
0.11 kW
5 l/s
1 ... 2.5 mm
2
18 ... 14 AWG
0.5 Nm / 4 lbf in
1.3 kg
463