Technical Data; Input Current Operation - Siemens SINAMICS G120P Hardware Installation Manual

Power module pm230 ip55/ul type 12
Hide thumbs Also See for SINAMICS G120P:
Table of Contents

Advertisement

6.3

Technical data

6.3.1

Input current operation

Note
The Power Module is only for operation at a maximum line impedance of 1% Vk. No line
reactor can be used with the Power Module.
Note
UL-certified fuses must be used
In order that the system is in compliance with UL, UL certified fuses, circuit breakers or self-
protected combination motor controllers must be used.
Note
The values for Low Overload (LO) are identical with those of the rated values.
Table 6- 1
PM230, IP55, frame sizes A, 3-ph. 380 V AC... 480 V
Order No. - with filter, Class A
Order No. - with filter Class B
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL
Power loss
Required cooling air flow
Cross section of line and motor cables
Tightening torque for line and motor cables
Weight
PM230 Power Module IP55
Hardware Installation Manual, 11/2014, A5E35319202B AA
6SL3223-...
...0DE13-7AA1
6SL3223-...
...0DE13-7BA1
0.37 kW
1.3 A
1.3 A
0.25 kW
0.9 A
0.9 A
3NA3803
10 A, Class J
0.06 kW
7 l/s
1 ... 2.5 mm
18 ... 14 AWG
0.5 Nm / 4.4 lbf in
4.3 kg
...0DE15-5AA1
...0DE15-5BA1
0.55 kW
1.8 A
1.7 A
0.37 kW
1.3 A
1.3 A
3NA3803
10 A, Class J
0.06 kW
7 l/s
1 ... 2.5 mm
2
2
18 ... 14 AWG
0.5 Nm / 4.4 lbf in
4.3 kg
Technical specifications
6.3 Technical data
...0DE17-5AA1
...0DE17-5BA1
0.75 kW
2.3 A
2.2 A
0.55 kW
1.8 A
1.7 A
3NA3803
10 A, Class J
0.06 kW
7 l/s
1 ... 2.5 mm
2
18 ... 14 AWG
0.5 Nm / 4.4 lbf in
4.3 kg
77