Commissioning
Initial commissioning using vector (chassis) as an example
3.6.4

Commissioning with STARTER (example)

The table below describes the steps for commissioning the example with
STARTER.
Table 3-9
Commissioning sequence with STARTER (example)
What to do?
1. Automatic
Operator action:
configuration
–>
"Project"
–>
Double-click "Automatic configuration"
–>
Follow the instructions provided in the Wizard
STARTER then automatically switches to offline
mode
2. Configure the
The supply must be configured.
supply
Name of supply
Click "Configure DDS"
2.1. Supply
The Wizard displays the data determined
Wizard
automatically from the electronic type plate.
You can now set the line/DC link identification.
You have to enter the device connection voltage
and rated line frequency.
This completes the configuration for the supply.
3. Configure
The drives must be configured individually.
drives
–>
"Drives"
"Configuration"
3.1. Control
You can activate the function modules.
structure
You can select the control type.
3.2. Power
The Wizard displays the data determined
section
automatically from the electronic type plate.
3.3. Drive setting
You can select the motor standard (IEC / NEMA)
and power section application (duty cycles).
3.4. Motor
You can enter the name of the motor (e.g.
equipment ID).
Enter motor data: Yes
Select motor type "1LA8".
3-70
How to do it?
–>
"Connect to target system"
–>
Double-click "Configuration"
–>
–>
Drive name
Double-click
–>
Click "Configure DDS"
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Comments
The DRIVE-CLiQ topology is
determined and the electronic
type plates are read. The
data is then transferred to
STARTER.
The next steps are carried out
offline.
–>
If the line environment or DC
link components are
changed, line/DC link
identification should be
repeated.
Caution
If a sinusoidal filter is
connected, it must be
activated here to prevent it
from being destroyed!
You can select a standard
motor from the list of motors
or you can enter the motor
data yourself. You can then
select the motor type.
E Siemens AG, 2004. All rights reserved