Acknowledging the Safety faults
Safety Integrated faults must be acknowledged as follows:
1. Remove the cause of the fault.
2. Deselect "Safe standstill (SH)".
3. Acknowledge the fault.
If Safety commissioning mode is exited when the Safety functions are switched off
(p0010 = value not equal to 95 when p9601 = p9801 = 0), all the Safety faults can
be acknowledged.
Once Safety commissioning mode has been reset (p0010 = 95), all the faults that
were previously present reappear.
Notice
The Safety faults can also be acknowledged (as with all other faults) by switching
the drive unit off and then on again (Power On).
If this action has not eliminated the fault cause, the fault is displayed again
immediately after power up.
Description of faults and alarms
Note
The faults and alarms for SINAMICS Safety Integrated are described in the
following documentation:
References:
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Commissioning the "SH" and "SBC" functions
/LH1/
SINAMICS S List Manual – Section 3.2
SINAMICS Safety Integrated (Booksize)
5-169