Table 4-17
Error values in DPV1 parameter responses, continued
Error
Meaning
value
0x78
Parameter %s [%s]: write access
only in the commissioning state,
drive configuration
(device: p0009 = 3).
0x79
Parameter %s [%s]: write access
only in the commissioning state,
definition of the drive type
(device: p0009 = 2).
0x7A
Parameter %s [%s]: write access
only in the commissioning state,
data set basis configuration
(device: p0009 = 4).
0x7B
Parameter %s [%s]: write access
only in the commissioning state,
device configuration
(device: p0009 = 1).
0x7C
Parameter %s [%s]: write access
only in the commissioning state,
device download
(device: p0009 = 29).
0x7D
Parameter %s [%s]: write access
only in the commissioning state,
device parameter reset
(device: p0009 = 30).
0x7E
Parameter %s [%s]: write access
only in the commissioning state,
device ready (device: p0009 = 0).
0x7F
Parameter %s [%s]: write access
only in the commissioning state,
device (device: p0009 not equal
to 0).
0x81
Parameter %s [%s] may not be
written in download.
0x82
Transfer of the control authority
(master) is inhibited by BI: p0806.
0x83
Parameter %s [%s]: Requested
BICO interconnection not possible
0x84
Parameter %s [%s]: Free BICO
interconnection inhibited by
p0717.
0x85
Parameter %s [%s]: Access
method not defined.
0xC8
Below the valid values.
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Communication via PROFIBUS
Comments
-
-
-
-
-
-
-
-
-
-
BICO output does not supply float values. The
BICO input, however, requires a float value.
-
-
Modification request for a value that, although
within "absolute" limits, is below the currently
valid lower limit.
Acyclic communication
Add.
informa-
tion
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4-129