Table 5-1
Commissioning the "SH" and "SBC" functions, continued
No.
Parameter
10
p9762 = "Value"
p9763 = "Value"
11
p0010 = Value
not equal to 95
12
-
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Set new safety password
Enter a new password
Confirm the new password
S
The new password is not valid until it has been entered in p9762 and
confirmed in p9763.
S
As of now, you must enter the new password in p9761 so that you can
change Safety parameters.
S
Changing the Safety password does not mean that you have to change the
checksums in p9799 and p9899.
Safety Integrated: exit commissioning mode
S
If at least one Safety monitoring function is enabled (p9601 = p9801 0 0),
the checksums are checked:
If the specified checksum on the Control Unit has not been correctly
adjusted, fault F01650 (Safety Integrated Control Unit: Acceptance test
required) is output with fault code 2000 and the user is prevented from
exiting Safety commissioning mode.
If the specified checksum on the Motor Module has not been correctly
adjusted, fault F01650 (Safety Integrated Control Unit: Acceptance test
required) is output with fault code 2001 and the user is prevented from
exiting Safety commissioning mode.
S
If a Safety monitoring function has not been enabled (p9601 = p9801 = 0),
Safety commissioning mode is exited without the checksums being
checked.
When Safety commissioning mode is exited, the following is carried out:
S
All the drive parameters are stored on the CompactFlash card.
S
The Safety parameters on the Motor Module are loaded by the Control Unit
and stored on the CompactFlash card.
S
The new Safety parameters are active on the Control Unit and Motor
Module.
Carrying out the acceptance test and creating the test certificate
Once Safety commissioning is complete, the commissioning engineer must
carry out an acceptance test for the enabled Safety monitoring functions.
The results of the acceptance test must be documented in an acceptance
certificate (see Section 5.7).
SINAMICS Safety Integrated (Booksize)
Commissioning the "SH" and "SBC" functions
Description / comments
5-167