◆ b: Application

Application parameters configure the source of the Up/Down command, timer functions, the Dwell function, the Droop
Control function, Energy Savings, and a variety of other application-related settings.
b1: Operation Mode Selection
No.
Name
b1-01
Speed Reference Selection
Up/Down Command
b1-02
Selection
b1-03
Stopping Method Selection
b1-06
Digital Input Reading
Up/Down Command
b1-08
Selection while in
Programming Mode
b1-14
Phase Order Selection
b2: Magnetic Flux Compensation
No.
Name
Magnetic Flux
b2-08
Compensation Value
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Parameters that were recently edited are listed here. The user can also select
parameters to appear here for quick access.
0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User
Parameters.
1: Save history of recently viewed parameters. Recently edited parameters will be
saved to A2-17 through A2-32 for quick access.
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option card
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option card
0: Ramp to stop
1: Coast to stop
4: Elevator Emergency Stop
Note: Setting 4 is available in the control mode CLV or CLV/PM for drives with
software versions PRG: 7017 or later. The setting is 0 or 1 for software version PRG:
7016.
0: Input status is read once and processed immediately (for quick response).
1: Input is read twice and processed only if the status is the same in both readings
(robust against noisy signals).
0: Up/Down command not accepted while in the Programming Mode.
1: Up/Down command accepted while in the Programming Mode.
2: Prohibit entering Programming Mode during run.
0: U-V-W
1: U-W-V
Sets the magnetic flux compensation as a percentage of the no-load current value
(E2-03).
Description
Description
Description
B Parameter Table
Setting
Default:
<5>
Min: A1-00
Max: S6-16
Default: 1
Min: 0
Max: 1
Setting
Default: 0
Min: 0
Max: 3
Default: 1
Min: 0
Max: 3
Default: 0
Min: 0
Max: 4
Default: 1
Min: 0
Max: 1
Default: 0
Min: 0
Max: 2
Default: 0
Min: 0
Max: 1
Setting
Default: 0%
Min: 0%
Max: 1000%