◆ S: Elevator Parameters

This section describes various functions and faults needed to operate an elevator application: braking sequence, slip
compensation, optimal adjustments at start and stop, Rescue Operation, and elevator-related faults.
S1-01: Zero Speed Level at Stop
Determines the speed to begin applying DC Injection (or Position Lock) when the drive is ramping to stop (b1-03 = 0).
Set as a percentage of the maximum output frequency (E1-04).
No.
S1-01
The function set by S1-01 changes depending on the control mode:
• V/f Control or OLV Control (A1-02 = 0, 2)
For these control modes, parameter S1-01 sets the starting speed for DC Injection Braking at stop. Once the output
speed falls below the setting of S1-01, the amount of DC Injection Braking current set in S1-03 is injected into the
motor for the time set in parameter S1-05.
• CLV Control or CLV/PM Control (A1-02 = 3, 7)
For these control modes, parameter S1-01 sets the starting speed for Position Lock at stop. Once the motor speed falls
below the setting of S1-01, Position Lock is enabled for the time set in parameter S1-05.
S1-02: DC Injection Current at Start
Determines the amount of current to use for DC Injection at start. Set as a percentage of the drive rated current.
No.
S1-02
S1-03: DC Injection Current at Stop
Determines the amount of current to use for DC Injection at stop. Set as a percentage of the drive rated current. When
using OLV Control, the DC injection current is determined by multiplying S1-03 by S3-25 or S3-26.
No.
S1-03
S1-04: DC Injection / Position Lock Time at Start
Determines how long the drive should perform DC Injection at start. In CLV and CLV/PM, S1-04 determines how long
Position Lock should be performed. During this time, the drive allows motor flux to develop, which is essential for
applying torque quickly once the brake is released. A setting of 0.00 disables S1-04.
No.
S1-04
S1-05: DC Injection / Position Lock Time at Stop
Determines how long the drive should perform DC Injection at stop. In CLV and CLV/PM, S1-05 determines how long
Position Lock should be performed. A setting of 0.00 disables S1-05.
No.
S1-05
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Parameter Name
Zero Speed Level at Stop
Parameter Name
DC Injection Current at Start
Parameter Name
DC Injection Current at Stop
Parameter Name
DC Injection / Position Lock Time at Start
Parameter Name
DC Injection / Position Lock Time at Stop
4 Start-Up Programming & Operation
Setting Range
0.000 to 9.999%
Determined by A1-02
Setting Range
0 to 100%
Setting Range
0 to 100%
Setting Range
0.00 to 10.00 s
Setting Range
0.00 to 10.00 s
Default
Default
50%
Default
50%
Default
0.40 s
4
Default
0.60 s
93