Connect To A Pc - YASKAWA L1000A Quick Start Manual

Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

Sinking/Sourcing Mode Selection for Safe Disable Inputs
Use jumper S3 on the terminal board to select between Sink mode, Source mode or external power supply for the Safe
Disable inputs H1 and H2 as shown in
Table 20 Safe Disable Input Sink / Source / External Power Supply Selection
Sinking Mode
Sourcing Mode

◆ Connect to a PC

This drive is equipped with a USB port (type-B).
The drive can connect to a USB port on a PC using a USB 2.0, AB-type cable (sold separately). After connecting the
drive to a PC, Yaskawa DriveWizard Plus software can be used to monitor drive performance and manage parameter
settings. Contact Yaskawa for more information on DriveWizard Plus.
Download and install the USB driver before connecting L1000A to a PC with the USB cable.
To obtain the driver and software of USB Copy Unit, CopyUnitManager and DriveWizardPlus, access these sites:
U.S.A: http://www.yaskawa.com
Other areas: contact a Yaskawa representative.
Figure 29
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Table 20
(Default: Sink mode, internal power supply).
Drive Internal Power Supply
Jumper S3
24 Vdc
HC
H1
H2
Jumper S3
24 Vdc
HC
H1
H2
USB Cable
(Type-AB)
(Type-B)
Figure 29 Connecting to a PC (USB)
External 24 Vdc Power Supply
Jumper S3
HC
External
24 Vdc
H1
H2
Jumper S3
HC
External
24 Vdc
H1
H2
(Type-A)
PC
Y E A
3 Electrical Installation
24 Vdc
24 Vdc
55
3

Advertisement