3 Electrical Installation
◆ Main Circuit Connection Diagram
Refer to the
Figure 7
when wiring the main circuit of the drive. Connections may vary based on drive capacity. The DC
power supply for the main circuit also provides power to the control circuit.
NOTICE: Do not use the negative DC bus terminal "-" as a ground terminal. This terminal is at high DC voltage potential. Improper
wiring connections could damage the drive.
NOTICE: Equipment Hazard. Separate motor and/or braking circuit wiring (terminals, U/T1, V/T2, W/T3, +3, +2, +1,(-), B1, B2, from all
other wiring. Place motor wiring within its own conduit or cable tray with appropriate divider, and use shielded motor cable where
appropriate. Improper wiring practices could result in malfunction of drive due to electrical interference.
CIMR-LU20008 to 20075
CIMR-LU40005 to 40039
CIMR-LU50003 to 50027
+1
Relay
+2
R/L1
+
S/L2
T/L3
–
Gate board
CIMR-LU20145 to 20180
CIMR-LU40075 to 40112
CIMR-LU50052 to 50077
+1
Relay
DC link
choke
R/L1
S/L2
T/L3
–
Gate board
28
B1 B2
Current
sensor
U/T1
V/T2
W/T3
Control
Operator
board
+3
Current
sensor
U/T1
+
V/T2
W/T3
YEA_co
mmon
Control
Operator
board
Figure 7 Drive main circuit configurations
CIMR-LU20085, 20115
CIMR-LU40045, 40060
CIMR-LU50032, 50041
+1
Relay
DC link
choke
R/L1
S/L2
T/L3
–
CIMR-LU20215 to 20415
CIMR-LU40150 to 40605
CIMR-LU50003 to 50200
CIMR-LU50099 to 50200
+1
Relay
DC link
choke
R/L1
S/L2
T/L3
–
24 V
Power
Supply
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
B1 B2
Current
sensor
+
Control
Gate board
Operator
board
+3
Current
sensor
+
Control
Gate board
Operator
board
U/T1
V/T2
W/T3
YEA_co
mmon
U/T1
V/T2
W/T3
YEA_co
mmon