Periodic Maintenance - YASKAWA L1000A Quick Start Manual

Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

Inspection Area
Check for any odor, discoloration, and rust. Make
sure connections are properly fastened and that no
Circuit Boards
dust or oil mist has accumulated on the surface of the
board.
Cooling Fan,
Circulation Fan,
• Check for abnormal oscillation or unusual noise.
Control Board
• Check for damaged or missing fan blades.
Cooling Fan
Inspect for dust or other foreign material collected on
Heatsink
the surface.
Inspect air intake and exhaust openings. They must
Air Duct
be free from obstruction and properly installed.
• Make sure data appears on the operator properly.
Digital Operator
• Inspect for dust or other foreign material that may
have collected on surrounding components.

◆ Periodic Maintenance

The drive has Maintenance Monitors that keep track of component wear. This feature provides advance maintenance
warning and eliminates the need to shut down the entire system for unexpected problems. The drive allows the user to
check predicted maintenance periods for the components listed below.
• Cooling Fan, Circulation Fan, Control Board Cooling Fan
• Electrolytic Capacitors
• Inrush Prevention Circuit
• IGBTs
For replacement parts, contact the distributor where the drive was purchased or contact Yaskawa directly.
Replacement Parts
Table 42
contains the estimated performance life of components that require replacement during the life of the drive. Only
use Yaskawa replacement parts for the appropriate drive model and revision.
Component
Cooling Fan, Circulation Fan
Electrolytic Capacitors
<1> The drive has few serviceable parts and may require complete drive replacement.
NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for the purpose of replacing
parts to maintain performance. Some parts may require more frequent replacement due to poor environments or rigorous use. Usage
conditions for estimated performance life:
Ambient temperature: Yearly average of 40°C (104°F) (IP00 enclosure)
Load factor: 80% maximum
Operation time: 24 hours a day
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Inspection Points
Cooling System Periodic Inspection
Display Periodic Inspection
Table 42 Estimated Performance Life
6 Periodic Inspection & Maintenance
Corrective Action
• Fix any loose connections.
• If an antistatic cloth or vacuum plunger cannot
be used, replace the board.
• Do not use any solvents to clean the board.
• Remove foreign particles and dust by sucking
them out with a vacuum cleaner to avoid
touching parts.
• The drive has few serviceable parts and may
require complete drive replacement.
Clean or replace the fan.
Remove foreign particles and dust by sucking
them out with a vacuum cleaner to avoid touching
parts.
• Visually inspect the area.
• Clear obstructions and clean air duct as
required.
• Contact a Yaskawa representative if there is any
trouble with the display or keypad.
• Clean the digital operator.
Estimated Performance Life
10 years
10 years
Checked
<1>
145
6