◆ n: Advanced Performance Set-Up

The n parameters are used to adjust more advanced performance characteristics such as speed feedback detection, Online
Tuning for motor line-to-line resistance, and PM motor control tuning.
n1: Hunting Prevention
No.
Name
n1-08
Leakage Current Vibration
Control Selection
<45>
<45> Available in drive software versions PRG: 7200 or later.
n2: Speed Feedback Detection Control (AFR) Tuning
No.
Name
Speed Feedback Detection
n2-01
Control (AFR) Gain
Speed Feedback Detection
n2-02
Control (AFR) Time
Constant 1
Speed Feedback Detection
n2-03
Control (AFR) Time
Constant 2
n5: Inertia Compensation
No.
Name
Inertia Compensation
n5-01
Selection
n5-02
Motor Acceleration Time
n5-03
Inertia Compensation Gain
Speed Feedback
n5-07
Compensation Selection
Speed Feedback
n5-08
Compensation Gain (P)
<4> Default setting value is dependent on the drive model (o2-04).
n6: Online Tuning
No.
Name
n6-01
Online Tuning Selection
n6-05
Online Tuning Gain
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
0: Method 1
1: Method 2
Sets the internal speed feedback detection control gain in the automatic frequency
regulator (AFR).
If hunting occurs, increase the set value. If response is low, decrease the set value.
Sets the time constant used for speed feedback detection control (AFR).
Sets the AFR time constant to be used during regen.
0: Disabled
1: Enabled
Sets the time required to accelerate the motor at 100% torque from 0 to the nominal
speed.
Sets the ratio between motor and load inertia. Lower this setting if overshoot occurs at
the end of acceleration.
0: Disabled
1: Enabled
2: Test Mode
Sets the proportional gain for the Speed Feedback Compensation.
0: Disabled
1: Line-to-line resistance tuning
2: Voltage correction.
Decrease this setting for motors with a relatively large rotor time constant.
If overload occurs, increase this setting slowly in increments of 0.1.
Description
Description
Description
Description
B Parameter Table
Setting
Default: 0
Min: 0
Max: 1
Setting
Default: 1.00
Min: 0.00
Max: 10.00
Default: 50 ms
Min: 0 ms
Max: 2000 ms
Default: 750 ms
Min: 0 ms
Max: 2000 ms
Setting
Default: 0
Min: 0
Max: 1
Default:
<4>
Min: 0.001 s
Max: 10.000 s
Default: 1.00
Min: 0.00
Max: 100.00
Default: 1
Min: 0
Max: 2
Default: 12.00
Min: 0.00
Max: 300.00
Setting
Default: 2
Min: 0
Max: 2
Default: 1.0
Min: 0.1
Max: 50.0
B
195