4 FUNCTIONS
4 - 49
5) Interrupt condition
Set the conditions under which events are issued.
Setting range: When RX, SB or RY is selected ON/OFF
6) Word device
Set the conditions under which events are issued when RWw or SW is
selected.
Setting range: 0 to 65535 (Decimal)
7) Interrupt (SI) No.
Set the intelligent function module interrupt pointer number.
(SI is an interrupt pointer for an intelligent function module and not a
device used in an actual program.)
Setting range: 0 to 15
POINT
Only one event issuance condition can be set for each interrupt program.
(b) Set the "PLC parameter" -- "PLC system" -- "Intelligent function module
setting" -- "Interrupt pointer settings".
1) "Interrupt pointer start No." on the PLC side.
Set the interrupt pointer start number for the CPU.
Setting range: 50 to 255
2) "Interrupt pointer No. of units" on the PLC side
Set the number of event issuance conditions specified in the "Interrupt
settings" of the Network parameters
Setting range: 1 to 16
3) "Start I/O No." on the Intelli. unit side
Set the start input/output number for the intelligent function module for
which the interrupt setting was performed.
Setting range: 0 to 0FF0 (H)
When RWr or SW is selected
0 to FFFF (Hexadecimal)
MELSEC-Q
Equal/Unequal
4 - 49