6 PARAMETER SETTINGS
6 - 45
(f) Set the station type using "Type".
Default value : Master station
Setting range: Master station
Example) Set to Master station.
(g) Set the CC-Link mode using "Mode".
Default value : Remote net(Ver.1 mode)
Setting range: Remote net(Ver.1 mode)
Example) Set to Remote I/O net mode.
(h) Set the data link status using "PLC down select", when a master station PLC
CPU error occurs.
Default value : Stop
Setting range: Stop
Example) Set to Stop.
(i)
Set whether the link scan for the sequence scan is synchronous or
asynchronous using "Scan mode setting".
Default value : Asynchronous
Setting range: Asynchronous
Example) Set to Asynchronous.
Master station (Duplex function)
Local station
Standby master station
Remote net(Ver.2 mode)
Remote net(Additional mode)
Remote I/O net mode
Off line
Continue
Synchronous
MELSEC-Q
6 - 45