Mitsubishi MELSEC Q Series User Manual page 185

Cc-link system master/local module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

6 PARAMETER SETTINGS
6 - 19
(f) Set the station type using "Type".
Default value : Master station
Setting range: Master station
Example) Set to Master station.
(g) Set the CC-Link mode using "Mode".
Default value : Remote net(Ver.1 mode)
Setting range: Remote net(Ver.1 mode)
Example) Set to Remote net (Ver.2 mode).
(h) Set the total number of connected stations in the CC-Link system including
reserved stations using "All connect count".
Default value : 64 (modules)
Setting range: 1 to 64 (modules)
Example) Set to 5 (modules).
(i) Set the number of retries using "Retry count", when a communication error
occurs.
Default value : 3 (times)
Setting range: 1 to 7 (times)
Example) Set to 5 (times).
(j)
Set the number of modules that can return to system operation by a single
link scan using "Automatic reconnection station count".
Default value : 1 (module)
Setting range: 1 to 10 (modules)
Example) Set to 2 (modules).
(k) Set the station number for the standby master station using "Standby master
station No.".
Default value : Blank (No standby master station specified)
Setting range: Blank, 1 to 64 (Blank: No standby master station
Example) Set to blank (No standby master station specified).
(l) Set the data link status using "PLC down select", when a master station PLC
CPU error occurs.
Default value : Stop
Setting range: Stop
Example) Set to Stop.
(m) Set whether the link scan for the sequence scan is synchronous or
asynchronous using "Scan mode setting".
Default value : Asynchronous
Setting range: Asynchronous
Example) Set to Asynchronous.
Master station (Duplex function)
Local station
Standby master station
Remote net(Ver.2 mode)
Remote net(Additional mode)
Remote I/O net mode
Off line
specified)
Continue
Synchronous
MELSEC-Q
6 - 19