5 DATA LINK PROCESSING TIME
5.2.2 Master station
5 - 7
remote device station (Ver. 1 compatible slave station)
(1) Master station (RX)
This indicates the time from the moment the signal is input to the remote device
station until the CPU device turns ON (OFF).
[Expression]
[Normal value]
(a) Asynchronous mode
SM + LS
1 + Remote device station processing time [ms]
SM: Master station sequence program scan time
LS: Link scan time (see Section 5.1)
(Example) When the sequence scan time for the master station is 20 ms, the link scan
time is 3 ms and the remote device station processing time is 1.5 ms.
SM + LS
= 20 + 3
= 24.5 [ms]
(b) Synchronous mode
(SM
n)
SM: Master station sequence program scan time
LS: Link scan time (see Section 5.1)
n:
(LS/SM)value when fractions following the decimal point are
rounded up to the next whole number
remote device station (RX)
1 + Remote device station processing time [ms]
1 + 1.5
1 + Remote device station processing time [ms]
MELSEC-Q
5 - 7