10 COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE
DEVICE STATIONS
1) A-D conversion of AJ65VBTCU-68ADV
D500
CH1 Digital output value
D501
CH2 Digital output value
2) D-A conversion of AJ65VBTCU-68DAVN
D510
CH1 Digital value setting
D511
CH2 Digital value setting
Q61P-A1
10 - 57

(2) Confirming the operation with the sequence program

Using the sequence program, confirm that the data link is being performed
normally.
1) Change the voltage input to the AJ65VBTCU-68ADV and confirm that the A-
D converted digital value also changes.
2) Set digital values to the AJ65VBTCU-68DAVN, and confirm that the voltages
converted from digital to analog are output.
Master
station
Q06HCPU
QJ61BT11N QX41 QY41P QX41
Terminal
resistor
AJ65VBTCU-68ADV
1)
Ver.1 compatible remote device station
Occupies 3 stations
QY41P
AJ65VBTCU-68DAVN
V
2)
Ver.2 compatible remote device station
(station number 1)
Occupies 1 station
MELSEC-Q
Terminal
resistor
(station number 4)
10 - 57