6 PARAMETER SETTINGS
6 - 8
(n) Set the link scan interval using "Delay information settings".
Default value : 0 (Not specified)
Setting range: 0 to 100 (Unit: 50 µ s)
Example) Set to 10 (500 µ s).
(o) Set the station data using "Station information settings".
Default value : Remote I/O station, single, Occupies 1 station, 32
Setting range: Station type - No setting
Example) Set the station data according to the system configuration
specified in Section 6.3.
points, or no setting for reserved stations/error
invalid.
Remote I/O station
Remote device station
Intelligent device station (including
local station and standby master
station)
Expanded cyclic setting (cannot be changed)-
single
Number of occupied stations -
No setting
Occupies 1 station
Occupies 2 stations
Occupies 3 stations
Occupies 4 stations
Remote station points (cannot be changed)-
32 points [when occupies 1 station]
64 points [when occupies 2 stations]
96 points [when occupies 3 stations]
128 points [when occupies 4 stations]
Reserved/invalid station select -
No setting
Reserved station
Invalid station (error invalid station)
Intelligent buffer select (word) -
No setting
Send
Receive
Automatic 0, 128 to 4096
MELSEC-Q
0, 64 to 4096
0, 64 to 4096
6 - 8