Mitsubishi MELSEC Q Series User Manual page 114

Cc-link system master/local module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

4 FUNCTIONS
Master station
Ver.2 mode
Ver. 2
Station number 1
compatible
Station number 2
remote
output RY
Station number 3
Station number 4
Station number 5
Station number 6
Station number 7
to
4 - 68
(1) Remote net ver.2 mode
This mode is designed to configure a new system.
The number of cyclic points can be increased as indicated below.
Per station, RX/RY can be increased to up to 128 points and RWw/RWr to up to
32 points.
Per CC-Link network, RX/RY can be increased to up to 8192 points and
RWw/RWr to up to 2048 points.
Remote I/O station
(Station number 1:
Occupies 1 station)
Output
POINT
(1) In the remote net ver. 2 mode, the remote registers of the remote I/O station are
set to 0 points.
(2) When the ver. 2 compatible slave station is added or deleted, the refresh
devices of the PLC CPU will vary by the number of points set to the added or
deleted slave station in the slave stations of the station numbers after the added
or deleted slave station. Confirm the varying number of points in Table 4.8.
[Setting method]
Using GX Developer, set the network parameters.
For more details on the setting, see Sections 6.3 to 6.5.
Remote device station
Ver. 2 compatible
(Station number 3:
(Station number 2:
Occupies 4 stations)
Occupies 1 station)
Remote output RY
quadruple
MELSEC-Q
Local station
Remote device station
Ver.2 mode
Ver. 2 compatible
(Station number 7:
Occupies 1 station)
Remote input RX
Station number 1
Station number 2
Station number 3
Station number 4
Station number 5
Station number 6
Remote output RY
Station number 7
to
double
octuple
4 - 68